Exhausts 

  • Exhausts acc. to G 442

    for gas pressure regulating and measuring stations

    • for harmlessly exhausting gases into the atmosphere
    • for connection to gas exhaust lines / manifolds
    • for connection to venting lines / manifolds
    • for connection to safety relief valves / manifold
    Technical Characteristics
    Type: acc. to G 442
    Nominal diameter exhaust: EO 25, DN 40, DN 50, DN 65, DN 80, DN 125, DN 150 and larger
    Nominal diameter connection pipes: EO 12, EO 15, EO 16, EO 18, EO 20, EO 22, EO 25, EO 28, DN 25, DN 32, DN 40, DN 50, DN 80, DN 100 and larger (following G 442)
    Materials: steel P235GH (ST 35.8 I) / (ST 37.4) or stainless steel 1.4301 (1.4541)
    Exhaust length: see table
    Connecting pipes: straight with plain end; L4 = 1100/1300 mm
    Medium: all gases acc. to DVGW worksheet G 260/I
    Acceptance: Primary Material Attestations DIN EN 10204 3.1
    Prices
    Bitte kontaktieren Sie uns unter info@tecon-systemtechnik.de oder +4926196389744. Danke!
    Nominal width Overall length Dimensions Item No. Price
    DN1 DN L1 L2 L3 L4 e DN1 Ø DN Ø Stahl
    EO12 EO25 * 240 100 60 1100 2,5 12,0 x 1,5 25,0 x 2,0 ABT251201E 80,00
    EO18 EO28 * 260 100 80 1100 3,0 18,0 x 2,0 28,0 x 2,0 ABT281801E 91,00
    EO20 40 350 160 130 1100 4,0 20,0 x 2,0 48,3 x 2,6 ABT402001E 93,00
    EO25 40 350 160 130 1100 4,0 25,0 x 2,0 48,3 x 2,6 ABT402501E 94,00
    25 40 * 350 160 130 1100 4,0 33,7 x 2,6 48,3 x 2,6 ABT402501A 88,00
    E028 40 350 160 130 1100 4,0 28,0 x 2,0 48,3 x 2,6 ABT402801E 101,00
    E028 50 450 200 160 1100 5,0 28,0 x 2,0 60,3 x 2,9 ABT502801E 102,00
    25 50 450 200 160 1100 5,0 33,7 x 2,6 60,3 x 2,9 ABT502501A 90,00
    32 50 * 450 200 160 1100 5,0 42,4 x 2,6 60,3 x 2,9 ABT503201A 100,00
    40 65 500 200 190 1100 8,0 48,3 x 2,6 76,1 x 2,9 ABT654001A 102,00
    50 80 * 560 250 200 1100 8,0 60,3 x 2,9 88,9 x 3,2 ABT805001A 112,00
    65 100 750 250 200 1100 8,0 76,1 x 2,9 114,3 x 3,6 ABT1006501A 230,00
    80 125 900 400 250 1300 10,0 88,9 x 3,2 139,7 x 4,0 ABT1258001A 235,00
    80 150 * 900 400 250 1300 10,0 88,9 x 3,2 163,3 x 4,5 ABT1508001A 270,00
    100 150 * 900 400 320 1300 12,0 114,3 x 3,6 168,3 x 4,5 ABT15010001A 293,00
    Inspection certificate DIN EN 10204 3.1 (for the basic material) APZ-AB 18,00

     

    Special Versions

    In addition to standard dimensions, customized versions are also available. If interested, please contact us for a free quotation.

    Note

    Our exhausts conform to the stipulations laid down by G 442.
    Explosion Protection Documentation acc. to §6 of the German Hazardous Substances Ordinance (GefStoffV) can likewise be submitted upon request.

    Further versions with pipe threads, flanges, curved pipes, dewatering sleeves, end caps, straight and angled clamp-connectors etc. are available upon request.

    In General

    Exhausts type A are conceived according to state of the art technology with an axially offset design between exhaust pipe and gas exhaust line for the removal of rainwater. As standard we offer exhausts in the nominal diameters EO 25 to DN 150 and in the materials steel and optionally stainless steel.

    Our exhausts type A are manufactured in the standard version with a straight connecting pipe downwards and with a total length of L4 = 1,100 mm (size nominal diameters 1,300 mm).
    The length L4 of 1,100/1,300 mm is designed for connecting the exhaust to an outlet opening at the outside of a building which protrudes out of a cabinet/ building at a height of ≥1,800 mm. When outlet openings are fitted higher than 1,800 mm, then the connecting pipe can be shortened according to needs. Here, care is to be taken to see that the ex-free zone underneath the exhaust L of 2,000 mm from ground level to the determined explosion protection zone underneath the exhaust is not below the minimum limit.

    The formula d x 10 is used for determining the explosion protection zone underneath the exhaust (see drawing dimension h). The system of rules from G 442 should be made use of in determining the whole explosion protection zone, which has to be presented in the so-called ex-zone plan as integral part of the explosion protection document.

    Exhausts in other dimensions and other designs, e.g. with 90-angled, longer connecting pipe or with closure at the lower end of the exhaust which are intended to be deployed for discharge pressures of ≥1.5 bar, can also be offered upon request.